Skip to main content

Diagram

CRAC Unit Diagram: Components & Airflow Explained

A visual CRAC unit diagram guide showing the main CRAC unit parts, chilled water CRAH units and data hall airflow paths that move heat out of a server room.

Updated 25 May 2026·9 min read·7 chapters

Summary

A CRAC unit diagram is useful because the words are often used loosely. Some sites call every precision cooling unit a CRAC unit, even when the indoor unit is technically a chilled water CRAH with no compressor.

The key question is simple: where does the heat go after it leaves the IT rack? In DX systems it goes into refrigerant and an outdoor condenser. In chilled water systems it goes into a water coil and back to central chiller plant. In a well-run data hall, airflow separation keeps hot return air out of the cold aisle.

For maintenance teams, a CRAC unit diagram should also identify service points: filters, coils, fans, compressor or valve set, condensate drain, humidifier, controller, alarm output and BMS connection. Those parts drive the inspection checklist on every service visit.

What is a CRAC unit?

A CRAC unit (Computer Room Air Conditioning unit) is a precision air conditioning system that controls temperature, humidity and airflow in server rooms, data centres and other critical rooms. Unlike comfort air conditioning built for people, a CRAC unit is built for heat-producing IT equipment that runs 24 hours a day, every day.

In HVAC terms, a CRAC unit is a high-sensible-cooling fan coil with tight control. Sensible cooling means it removes heat without removing much moisture, because IT rooms need stable humidity rather than heavy dehumidification. People search for this equipment as a CRAC unit, CRAC system, CRAC AC unit, CRAC cooling unit or CRAC air conditioning; they all describe the same class of precision cooling.

The core CRAC unit parts are similar across brands. The diagram and tables below show how those parts sit in the heat path and what each one does during a service visit.

  • Air filters: clean the return air before it reaches the coil.
  • Cooling coil: transfers heat from room air into refrigerant or chilled water.
  • Supply fans: push cooled air to the racks (EC fans on modern units).
  • Compressor (DX) or chilled water valve (CHW): drives the cooling stage.
  • Condensate tray and drain: remove water that forms on the coil.
  • Humidifier: holds room humidity inside the target band.
  • Controller, alarms and BMS points: run setpoints and report faults.

1. What a CRAC unit diagram should show

A useful CRAC diagram shows the heat path, not only the box shape. The heat starts at servers and network gear, passes into the room air, enters the cooling unit, crosses the cooling coil, and is rejected to a condenser, cooling tower, dry cooler or chiller plant.

The diagram should separate three ideas: the air path inside the room, the refrigeration or chilled water circuit inside the cooling plant, and the controls layer that links alarms, sensors, BMS points and unit rotation.

The most useful diagrams label the parts that technicians inspect during CRAC maintenance: filter bank, return air sensor, supply fan, cooling coil, compressor or chilled water valve, condensate tray, humidifier, controller, alarm relay and BMS point set.

Practical tip

If a diagram does not show hot air returning to the unit and cold air reaching the rack face, it is not enough for maintenance planning.

2. DX CRAC unit diagram

A direct expansion CRAC unit has an indoor unit with a cooling coil, fans, controls and usually a compressor. Refrigerant carries heat from the indoor coil to an outdoor condenser. This is the common pattern for small and mid-size server rooms because it does not need central chilled water plant.

DX CRAC unit diagramServer roomIT racksCold aisleDX CRACCooling coilCompressorOutdoorcondenser
DX CRAC heat path: server heat to return air, indoor coil, compressor, outdoor condenser and back to supply air.
PartWhat it doesService check
Return air pathBrings warm room air back to the unitCheck blocked grilles, bypass air and hot spots
Cooling coilTransfers heat from air into refrigerantClean coil face and check pressure drop
CompressorMoves refrigerant through the circuitCheck current draw, superheat and fault history
Outdoor condenserRejects heat to outside airClean coil, test fans and confirm clear airflow
Controls and alarmsRuns setpoints, staging and alertsTest alarm outputs and BMS point mapping
DX CRAC maintenance points

3. CHW CRAH diagram

A chilled water CRAH has no compressor inside the room unit. The indoor unit is a fan coil: warm return air passes across a chilled water coil, and heat is carried back to the chiller plant through the water loop. Many Australian sites still call this a CRAC because the service category is familiar.

Chilled water CRAH diagramCRAH unitWater coilEC fansChilled waterloopChillerplantNo compressor in the room unit
CHW CRAH heat path: room air crosses a chilled water coil, then heat returns to central chiller plant.

The maintenance focus changes with CHW systems. Refrigerant work moves to the chiller plant, while the indoor unit service focuses on valve control, actuator response, coil condition, condensate, fan performance and temperature delta across the chilled water loop.

4. Hot-aisle and cold-aisle airflow diagram

The room airflow path matters as much as the cooling unit. Cold air must reach the rack intake face without mixing with hot exhaust air. Hot aisle and cold aisle layouts, blanking panels and containment all reduce bypass and recirculation.

Hot aisle and cold aisle airflow diagramRack rowRack rowRack rowColdaisleColdaisleHotaisleCold supply air stays separate from hot return air
Hot-aisle/cold-aisle airflow: cold supply air feeds rack intakes, hot exhaust air returns to CRAC or CRAH units.

Caution

A CRAC unit can be correctly serviced and still fail to cool the room if rack airflow is wrong. Missing blanking panels, open cable cut-outs and poor containment often cause the fault.

5. CRAC vs CRAH in one table

TopicDX CRACCHW CRAH
Heat carrierRefrigerant between indoor unit and outdoor condenserChilled water between room unit and chiller plant
Compressor locationUsually inside the CRAC or paired outdoor systemAt the chiller plant, not in the room unit
Best fitSmall to mid-size server rooms and edge sitesLarge data halls and high-density rooms with central plant
Service focusRefrigerant circuit, compressor, condenser and airflowValves, coil, water delta, fans and controls
Compliance focusAS/NZS 5149, ARC licensing, AS/NZS 1668.2AS/NZS 1668.2, AS/NZS 3666 where water systems apply
CRAC vs CRAH quick comparison

6. What to check during a site walk

When reviewing a CRAC or CRAH room, follow the heat path. Start at the rack intake temperature, then inspect the hot aisle, return path, filter condition, coil face, condensate, fans, control panel, alarms and heat rejection plant.

  1. Confirm the unit type: DX CRAC, CDW CRAC, CHW CRAH, in-row or rear-door heat exchanger.
  2. Record supply air and return air temperatures at each unit.
  3. Check rack intake temperature at the top, middle and bottom of each rack row.
  4. Look for bypass air through open floor tiles, missing blanking panels and cable cut-outs.
  5. Check filters, coil cleanliness, fan speed, condensate and alarm history.
  6. Confirm the heat rejection plant is working: condenser, cooling tower, dry cooler or chiller.

Frequently asked questions

What is a CRAC unit?

A CRAC unit (Computer Room Air Conditioning unit) is a precision air conditioning system that controls temperature, humidity and airflow for IT equipment in server rooms and data centres. It runs continuously and holds a tighter temperature and humidity band than comfort air conditioning, because the load is heat-producing hardware rather than people.

What is a CRAC unit in HVAC?

In HVAC terms a CRAC unit is a high-sensible-cooling fan coil with close control. It removes mostly sensible heat (temperature) without heavy dehumidification, so the room stays inside a stable humidity band. A DX CRAC has its own refrigerant circuit and compressor; a chilled water unit (often called a CRAH) uses a water coil fed from central chiller plant.

What are the main parts of a CRAC unit?

The main CRAC unit parts are the air filter bank, cooling coil, supply fans, a compressor (DX) or chilled water valve set (CHW), a condensate tray and drain, a humidifier, the controller, and the alarm or BMS connection. Each of these is a checkpoint on a CRAC maintenance visit, which is why a labelled CRAC unit diagram doubles as an inspection map.

What is the difference between a CRAC unit and a CRAH unit?

A CRAC unit cools using a refrigerant circuit, usually with a compressor in or near the unit, and rejects heat to an outdoor condenser. A CRAH unit has no compressor in the room: it passes air across a chilled water coil and sends the heat back to central chiller plant. DX CRAC suits small to mid-size rooms; chilled water CRAH suits large data halls with central plant.

How does a CRAC unit work?

A CRAC unit draws warm return air from the room, passes it through a filter and across a cooling coil, then delivers cooled air back to the racks. In a DX unit the coil transfers heat into refrigerant that a compressor moves to an outdoor condenser. In a chilled water unit the coil transfers heat into water that returns to the chiller plant. The controller holds the supply temperature and humidity at setpoint and raises alarms on faults.